🇨🇴⚖️ La Rama Judicial valida a Ariel en prueba de concepto de IA. Conoce los resultados aquí

CNO - REPORTE DE PRUEBAS LVRT Y HVRT 1 de 2024

CNO - Consejo Nacional de Operación

Icono de documento PDF

Descargar PDF

Disponible

Detalles

Título
CNO - REPORTE DE PRUEBAS LVRT Y HVRT 1 de 2024
Autor
CNO - Consejo Nacional de Operación
Categoría
Infralegal
Área del derecho
Servicios Públicos
Año
2024

REV DESCRIPCIÓN ELABORADOR REVISOR APROBADOR FECHA 00 ISSUED FOR CONSTRUCTION K. Fan N. Gonz ález M. Yu 15/07/2022

Engineering &

Construction

N. González K. Fan M. Yu

COLLABORATORS VERIFIED BY V ALIDATED BY GROUP TYPE COUNTRY . PROJECT CODE PROGRESSIVE REVISION MYU R C O 3 7 7 8 2 0 4 1 0 0

CLASSIFICATION: FOR VALIDATION UTILIZATION SCOPE: FOR CONSTRUCTION

SOLAR PACK VALIDATION

  • J. Rincón R. Martinez

COLABORADOR VERIFICADOR VALIDADOR REPORTE DE PRUEBAS LVRT Y HVRT PARQUE FOTOVOLTAICO LA MATA Y LA UNIÓNFRT TESTING FOR THE VERIFICATION OF COMPLIANCE

OF GRID CONNECTED POWER CONVERSION SYSTEM

WITH:

FGW TG3: DETERMINATION OF THE ELECTRICAL

CHARACTERISTICS OF POWER GENERATING UNITS

AND SYSTEMS, STORAGE SYSTEMS AS WELL FOR

THEIR COMPONENTS IN MV, HV AND EHV GRIDS.

(REV. 25 DATED ON 01/09/2018 + SUPPLEMENT 1 DATED

ON 22/01/2019)

Procedure: PE.T-LE-62

Test Report Number ....................................... : 2221 / 0124 – 1 - Att1 Rev0 Type ................................................................. : 3 Phase Grid Connected PV Inverter Tested Model .................................................. : SG3125HV-30 Variant Models ................................................ : SG3000HV-30 and SG3400HV-30

APPLICANT Name ............................................................. : SUNGROW POWER SUPPLY CO., LTD.

Address ......................................................... : No.1699 Xiyou Rd., New & High Technology Industrial Development Zone Hefei, Anhui 230088, P. R. China TESTING LABORATORY Name ............................................................. : SGS Tecnos, S.A. (Electrical Testing Laboratory)

Address ......................................................... : No.1699 Xiyou Rd., New & High Technology Industrial Development Zone Hefei, Anhui 230088, P. R. China TESTING LABORATORY Name ............................................................. : SGS Tecnos, S.A. (Electrical Testing Laboratory) Address ......................................................... : C/ Trespaderne, 29 - Edificio Barajas 1 28042 Madrid (Spain) Conducted (tested) by ................................... : Michael Tong (Project Engineer) Reviewed and Approved by .......................... : Omar Kalim (Technical Reviewer) Date of issue ................................................. : 2021/08/24 Number of pages .......................................... : 327Report N. 2221 / 0124 - 1 Attachment I Page 2 of 327 Rev. 0 FRT test in FGW-TG3+SP1: Grid Fault Tests Results

Important Note:

  • This document is issued by the Company under its General Conditions of service accessible at

http://www.sgs.com/terms_and_conditions.htm. Attention is drawn to the limitation of l iability, indemnification and jurisdiction issues defined therein. Any holder of this document is advised that information contained hereon reflects the Company's findings at the time of its intervention only and within the limits of Client's instructions, if any. The Company's sole responsibility is to its Client and this document does not exonerate parties to a transaction from exercising all their rights and obligations under the transaction documents.

  • Any unauthorized alteration, forgery or falsification of the content or appearance of this document is unlawful, and offenders may be prosecuted to the fullest extent of the law.
  • Unless otherwise stated the results shown in this test report refer only to the sample(s) tested as received. Information of derived or extension models of the range as provided by the applicant, (if any), is included in this report only for informative purposes. The Company SGS shall not be liable for any incorrect results arising from unclear, erroneous, incomplete, misleading or false information

received. Information of derived or extension models of the range as provided by the applicant, (if any), is included in this report only for informative purposes. The Company SGS shall not be liable for any incorrect results arising from unclear, erroneous, incomplete, misleading or false information provided by Client. This document cannot be reproduced except in full, without prior approval of the Company.

Historical Revision:

Document Version Date Resume

2221/0124-1-Att1 Rev0

2021/08/24

First issuanceReport N. 2221 / 0124 - 1 Attachment I Page 3 of 327 Rev. 0 FRT test in FGW-TG3+SP1: Grid Fault Tests Results

INDEX

1 SCOPE .............................................................................................................................................. 5 2 GENERAL INFORMATION ..................................................................................................................... 6 2.1 Testing Period and Climatic conditions .......................................................................... 6 2.2 Equipment under Testing ............................................................................................... 6 2.2.1 Reference Values ........................................................................................................... 9 2.3 Test equipment list ....................................................................................................... 10 2.4 Measurement uncertainty and Data Sampling Rates .................................................. 11 2.5 Test set up .................................................................................................................... 11 3 RESPONSE DURING GRID FAULTS ...................................................................................................... 12 3.1 LVRT ............................................................................................................................ 16 3.1.1 No load tests ................................................................................................................ 16 3.1.1.1 Fault type: 3 phases; Dip depth 0 %Un ................................................................... 16 3.1.1.2 Fault type: 2 phases; Dip depth 0 %Un ................................................................... 18 3.1.1.3 Fault type: 3 phases; Dip depth 25 %Un ................................................................. 20 3.1.1.4 Fault type: 2 phases; Dip depth 25 %Un ................................................................. 22 3.1.1.5 Fault type: 3 phases; Dip depth 50 %Un ................................................................. 24

3.1.1.4 Fault type: 2 phases; Dip depth 25 %Un ................................................................. 22 3.1.1.5 Fault type: 3 phases; Dip depth 50 %Un ................................................................. 24 3.1.1.6 Fault type: 2 phases; Dip depth 50 %Un ................................................................. 26 3.1.1.7 Fault type: 3 phases; Dip depth 75 %Un ................................................................. 28 3.1.1.8 Fault type: 2 phases; Dip depth 75 %Un ................................................................. 30 3.1.1.9 Fault type: 3 phases; Dip depth 80 %Un ................................................................. 32 3.1.1.10 Fault type: 2 phases; Dip depth 80 %Un ................................................................. 34 3.1.1.11 Fault type: 3 phases; Dip depth 85 %Un ................................................................. 36 3.1.2 Load tests: Dip depth 0 %Un ....................................................................................... 38 3.1.2.1 Test 0.1 Fault type: 3 phases, Full load ................................................................... 38 3.1.2.2 Test 0.2 Fault type: 3 phases, Partial load .............................................................. 46 3.1.2.3 Test 0.3 Fault type: 2 phases, Full load ................................................................... 54 3.1.2.4 Test 0.4 Fault type: 2 phases, Partial load .............................................................. 62 3.1.3 Load tests: Dip depth 25 %Un ..................................................................................... 70 3.1.3.1 Test 25.1 Fault type: 3 phases, Full load ................................................................. 70 3.1.3.2 Test 25.2 Fault type: 3 phases, Partial load ............................................................ 78 3.1.3.3 Test 25.3 Fault type: 3 phases, Full load, Test sequence for multiple faults........... 86 3.1.3.4 Test 25.4 Fault type: 2 phases, Full load ................................................................. 94

3.1.3.3 Test 25.3 Fault type: 3 phases, Full load, Test sequence for multiple faults........... 86 3.1.3.4 Test 25.4 Fault type: 2 phases, Full load ................................................................. 94 3.1.3.5 Test 25.5 Fault type: 2 phases, Partial load .......................................................... 102 3.1.4 Load tests: Dip depth 50 %Un ................................................................................... 110 3.1.4.1 Test 50.1 Fault type: 3 phases, Full load ............................................................... 110 3.1.4.2 Test 50.2 Fault type: 3 phases, Partial load .......................................................... 118 3.1.4.3 Test 50.3 Fault type: 2 phases, Full load ............................................................... 126 3.1.4.4 Test 50.4 Fault type: 2 phases, Partial load .......................................................... 134 3.1.4.5 Test 50.5 Fault type: 3 phases, Full load, Limited dynamic grid support .............. 142 3.1.4.6 Test 50.6 Fault type: 2 phases, Full load, Limited dynamic grid support .............. 150 3.1.5 Load tests: Dip depth 75 %Un ................................................................................... 158 3.1.5.1 Test 75.1 Fault type: 3 phases, Full load ............................................................... 158 3.1.5.2 Test 75.2 Fault type: 3 phases, Partial load .......................................................... 166 3.1.5.3 Test 75.3 Fault type: 3 phases, Partial load, PF = 0.80 over-excited .................... 174 3.1.5.4 Test 75.4 Fault type: 3 phases, Partial load, PF = 0.80 under-excited ................. 182 3.1.5.5 Test 75.5 Fault type: 3 phases, Partial load, k = 4 ................................................ 190 3.1.5.6 Test 75.6 Fault type: 2 phases, Full load ............................................................... 198

3.1.5.5 Test 75.5 Fault type: 3 phases, Partial load, k = 4 ................................................ 190 3.1.5.6 Test 75.6 Fault type: 2 phases, Full load ............................................................... 198 3.1.5.7 Test 75.7 Fault type: 2 phases, Partial load .......................................................... 206 3.1.5.8 Test 75.8 Fault type: 2 phases, Partial load, k = 4 ................................................ 214 3.1.6 Load tests: Dip depth 80 %Un ................................................................................... 222 3.1.6.1 Test 80.1 Fault type: 3 phases, Full load, Limited dynamic grid support .............. 222 3.1.6.2 Test 80.2 Fault type: 2 phases, Full load, Limited dynamic grid support, k = 0 .... 230 3.1.7 Load tests: Dip depth 85 %Un ................................................................................... 238 3.1.7.1 Test 85.1 Fault type: 3 phases, Full load ............................................................... 238 3.2 HVRT .......................................................................................................................... 246 3.2.1 No load tests .............................................................................................................. 246 3.2.1.1 Test 115.0, 3 phases; Dip depth 115 %Un ............................................................ 246Report N. 2221 / 0124 - 1 Attachment I Page 4 of 327 Rev. 0 FRT test in FGW-TG3+SP1: Grid Fault Tests Results

3.2.1.2 Test 110.0.1, 2 phases; Dip depth 110 %Un ......................................................... 248 3.2.1.3 Test 110.0.2, 3 phases; Dip depth 110 %Un ......................................................... 250 3.2.2 Load tests ................................................................................................................... 252 3.2.2.1 Test 115.1, Fault type: 3 phases, Full load ............................................................ 252

3.2.2 Load tests ................................................................................................................... 252 3.2.2.1 Test 115.1, Fault type: 3 phases, Full load ............................................................ 252 3.2.2.2 Test 115.2 Fault type: 3 phases, Partial load ........................................................ 260 3.2.2.3 Test 110.1 Fault type: 2 phases, Full load ............................................................. 268 3.2.2.4 Test 110.2 Fault type: 2 phases, Partial load ........................................................ 276 3.2.2.5 Test 110.3 Fault type: 3 phases, Partial load ........................................................ 284 3.3 Additional abrupt voltage change tests ...................................................................... 292 3.3.1 No load tests .............................................................................................................. 292 3.3.1.1 Test 95.0, 3 phases; Voltage changed from 0.95 Un to 1.05 Un .......................... 292 3.3.1.2 Test 105.0, 3 phases; Voltage changed from 1.05 Un to 0.95 Un ........................ 294 3.3.2 Load tests: Voltage changed from 0.95 Un to 1.05 Un .............................................. 296 3.3.2.1 Test 95.1 Fault type: 3 phases, Full load ............................................................... 296 3.3.2.2 Test 95.2 Fault type: 3 phases, Partial load .......................................................... 304 3.3.3 Load tests: Voltage changed from 1.05 Un to 0.95 Un .............................................. 312 3.3.3.1 Test 105.1 Fault type: 3 phases, Full load ............................................................. 312 3.3.3.2 Test 105.2 Fault type: 3 phases, Partial load ........................................................ 320Report N. 2221 / 0124 - 1 Attachment I Page 5 of 327 Rev. 0 FRT test in FGW-TG3+SP1: Grid Fault Tests Results

1 SCOPE

Attachment I Page 5 of 327 Rev. 0 FRT test in FGW-TG3+SP1: Grid Fault Tests Results

1 SCOPE

SGS Tecnos, S.A. (Electrical Testing Laboratory) has been contracted by SUNGROW POWER SUPPLY CO., LTD. to perform ‘RESPONSE DURING GRID FAULTS’ testing according to FGW-TG3: Technical Guidelines for Power Generating Units and Systems. TG3 (Revision 25 Dated 01/09/2018 + Supplement 1 Dated 22/01/2019): Determination of Electrical Characteristics of Power Generating Units and Systems, Storage Systems as well for their Components in MV, HV and EHV grids.

The following standards are covered with testing of FGW-TG3 (Revision 25 Dated 01/09/2018) (): - VDE-AR-N 4110: 2018-11. Technical requirements for the connection and operation of customer installations to the medium voltage network (TAR medium voltage). - VDE-AR-N 4120: 2018-11. Technical requirements for the connection and operation of customer installations to the high voltage network (TAR high voltage).

() As stated in chapter 11.2.1 of both covered standards.

This is an attachment to Test Report 2221/0124-1 that has been prepared to show the results for RESPONSE DURING GRID FAULTS test (clause 4.6 of the standard).Report N. 2221 / 0124 - 1 Attachment I Page 6 of 327 Rev. 0 FRT test in FGW-TG3+SP1: Grid Fault Tests Results

2 GENERAL INFORMATION

2.1 TESTING PERIOD AND CLIMATIC CONDITIONS

The necessary testing has been performed between the 25th of September of 2020 to 10th of November of 2020 and on 20th of March of 2021 and on 19th of August of 2021.

2.1 TESTING PERIOD AND CLIMATIC CONDITIONS

The necessary testing has been performed between the 25th of September of 2020 to 10th of November of 2020 and on 20th of March of 2021 and on 19th of August of 2021.

All the tests and checks have been performed at 25 ± 10 ºC, 90 kPa ± 10 kPa and 50 %RH ± 20 %RH.

SITE TEST Name ............................................................. : Shanghai Testing & Inspection Institute for Electrical Equipment Co., Ltd Address ......................................................... : 505 Wuning Road, Shanghai/358 North Huancheng Road, Shanghai, P.R. China

2.2 EQUIPMENT UNDER TESTING

Apparatus type ............................................ : Grid Connected PV Inverter Installation ................................................... : 3 Phase ~ / Fixed installation Manufacturer ............................................... : SUNGROW POWER SUPPLY CO., LTD. Trade mark .................................................. : Model / Type reference ............................... : SG3125HV-30 Serial Number ............................................. : A20B2902750 Software Version ......................................... : LCD_SG3125HV-30_V1_A, DSP_SG3125HV-30_V1_A Rated Characteristics .................................. : Input: 1500 Vdc Max (875-1300 Vdc MPPT); 3997 Adc Max Output: 3~ 600 Vac; 50 Hz; 3007 Aac() (3308 Aac Max); 3125 KW (3437 kVA Max). () The rated output current is calculated using rated voltage and power.

Date of manufacturing: 2020

Test item particulars Input ............................................................ : DC Output ........................................................... 3~/PE Class of protection against electric shock ... : Class I Degree of protection against moisture ........ : IP65 Type of connection to the main supply ....... : Three-phase – Fixed installation Cooling group .............................................. : Forced ventilation (Fans) Modular ....................................................... : Yes

Output ........................................................... 3~/PE Class of protection against electric shock ... : Class I Degree of protection against moisture ........ : IP65 Type of connection to the main supply ....... : Three-phase – Fixed installation Cooling group .............................................. : Forced ventilation (Fans) Modular ....................................................... : Yes Internal Transformer .................................... : NoReport N. 2221 / 0124 - 1 Attachment I Page 7 of 327 Rev. 0 FRT test in FGW-TG3+SP1: Grid Fault Tests Results

Copy of marking plate:

Note:

1. The above markings are the minimum requirements required by the safety standard. For t he final production samples, the additional markings which do not give rise to misunderstanding may be added.

2. Label is attached on the side surface of enclosure and visible after installation .

3. Labels of other models are as the same with SG3125HV-30’s except the parameters of rating.

Equipment under testing:

- SG3125HV-30

The variants models are:

- SG3000HV-30

- SG3400HV-30

Note: The EUT is composed of two same structure modules, only one module was tested in all tests. This corresponds with half of the rated power of the complete unit.Report N. 2221 / 0124 - 1

Attachment I Page 8 of 327 Rev. 0 FRT test in FGW-TG3+SP1: Grid Fault Tests Results

The complete structure of two modules can be included in this test report without tests because the following features dont change regarding to results obtained over just one model:

  • Same connection system and hardware topology. - Same control algorithm. - Output power within 1/√10 and 2 times of the rated output power or the EUT or Modular inverters.
  • Same Firmware Version.

The results obtained apply only to the particular sample tested that is the subject of the present test report.

  • Same control algorithm. - Output power within 1/√10 and 2 times of the rated output power or the EUT or Modular inverters.
  • Same Firmware Version.

The results obtained apply only to the particular sample tested that is the subject of the present test report.

The most unfavorable result values of the verifications and tests performed are contained herein. Throughout this report a point (comma) is used as the decimal separator.

The parameters of the PV Inverter models are as following:

Product Model SG3125HV-30 SG3000HV-30 SG3400HV-30 Input (DC) Max.DC Voltage 1500 V 1500 V 1500 V MPPT Voltage Range 875-1300 V 875 -1300 V 875 - 1300 V Max Input Current 3997 A 3500 A 3997 A Max short-circuit Current (Isc) 10000 A 10000 A 10000 A Output (AC) Max AC Output Power 3437 kVA 3000 kVA 3437 kVA Max AC Output Current 3308 A 2887 A 3308 A Rated AC Output Power 3125 kW 3000 kW 3437 kW Rated AC Output Current 3007 A 2887 A 3308 A Rated Grid Voltage 600 V (3 ~ ) 600 V (3 ~ ) 600 V (3 ~ ) Rated Frequency 50 Hz 50 Hz 50 Hz Power Factor [-0.8, 0.8] [-0.8, 0.8] [-0.8, 0.8] Operating Temperature Range -35ºC ~ 60ºC -35ºC ~ 60ºC -35ºC ~ 60ºC Degree of Protection IP65 IP65 IP65 Protective Class Class I Class I Class IReport N. 2221 / 0124 - 1 Attachment I Page 9 of 327 Rev. 0 FRT test in FGW-TG3+SP1: Grid Fault Tests Results

Degree of Protection IP65 IP65 IP65 Protective Class Class I Class I Class IReport N. 2221 / 0124 - 1 Attachment I Page 9 of 327 Rev. 0 FRT test in FGW-TG3+SP1: Grid Fault Tests Results

2.2.1 Reference Values

The values presented in the following table have been used for calculation of referenced values (p.u.; %) through the report.

Reference Values for the whole EUT Rated power, Pn in kW 3125 Rated apparent power, Sn in kVA 3125 Maximum power, Pmax in kW 3437 Maximum apparent power, Smax in kVA 3437 Rated wind speed (only WT), vn in m/s N/A Rated current (determined), In in A(1) 3007 Rated output voltage, (phase to phase) Un in Vac 600 Rated output voltage, (Line to Neutral) Un in Vac (2) 346.4

Note: In this report p.u. values are calculated as follows: -For Active & Reactive Power p.u values are reference to Pn -For Currents p.u values, the reference is always In -For Voltages p.u values, the reference is always Un

Reference Values for the tested one module of the EUT Rated power, Pn in kW 1562.5 Rated apparent power, Sn in kVA 1562.5 Maximum power, Pmax in kW 1718.5 Maximum apparent power, Smax in kVA 1718.5 Rated wind speed (only WT), vn in m/s N/A Rated current (determined), In in A(1) 1503.5 Rated output voltage, (phase to phase) Un in Vac 600 Rated output voltage, (Line to Neutral) Un in Vac(2) 346.4

Note: In this report p.u. values are calculated as follows: -For Active & Reactive Power p.u values are reference to Pn

Rated output voltage, (phase to phase) Un in Vac 600 Rated output voltage, (Line to Neutral) Un in Vac(2) 346.4

Note: In this report p.u. values are calculated as follows: -For Active & Reactive Power p.u values are reference to Pn -For Currents p.u values, the reference is always In -For Voltages p.u values, the reference is always Un

(1) The rated output current is calculated using rated voltage and power. (2) Virtual neutral had been used to change 3/PE wiring to 3/N/PE wiring since limitation of the test bench.Report N. 2221 / 0124 - 1 Attachment I Page 10 of 327 Rev. 0 FRT test in FGW-TG3+SP1: Grid Fault Tests Results

2.3 TEST EQUIPMENT LIST

Owner No. EQUIPMENT MARK/MODEL S/N CALIBRATION PERIOD 1 Wave Recorder Yokogawa / DL850E 91V809389 2019/11/27 to 2020/11/26 2020/11/04 to 2021/11/03 2 Power Analyzer Yokogawa / WT3000E 91W513917 2020/09/08 to 2021/09/07 3 Power Analyzer DEWE2-A7 B4190047-CHN 2019/11/15 to 2020/11/14 4 Power Analyzer DEWE2-A7 B419007-CHN 2020/09/29 to 2021/09/28 5 Current Probe Senshe / CHB-3KB/SP10 SS1907194D00 1 2019/10/28 to 2020/10/27 2020/11/03 to 2021/11/02 6 Current Probe Senshe / CHB-3KB/SP10 SS1907194D00 6 2019/10/28 to 2020/10/27 2020/11/03 to 2021/11/02

2020/11/03 to 2021/11/02 6 Current Probe Senshe / CHB-3KB/SP10 SS1907194D00 6 2019/10/28 to 2020/10/27 2020/11/03 to 2021/11/02 7 Current Probe Senshe / CHB-3KB/SP10 SS1907194D00 4 2019/10/28 to 2020/10/27 2020/11/03 to 2021/11/02 8 Current Probe Senshe / CHB-3KB/SP10 SS1907194D00 5 2019/11/15 to 2020/10/27 2020/11/03 to 2021/11/02 9 Voltage Probe Yokogawa / 701926 1905983 2019/11/14 to 2020/11/13 2020/10/28 to 2021/10/27 10 Voltage Probe Yokogawa / 701926 1905979 2019/11/14 to 2020/11/13 2020/11/03 to 2021/11/02 11 Voltage Probe Yokogawa / 701926 1905988 2019/11/14 to 2020/11/13 2020/10/28 to 2021/10/27 12 Temperature Chamber MEITAIKE / MHPW-192-DW MT2019102501 2019/11/15 to 2020/11/14 2020/11/14 to 2021/11/13 13 Temperature & Humidity meter Shanghaiqixiang / HM10 090 2019/11/14 to 2020/11/13 2020/10/28 to 2021/10/27 14 Multimeter Fluke / 289C SHES500602 2020/06/12 to 2021/06/11 2021/06/06 to 2022/06/05

2020/10/28 to 2021/10/27 14 Multimeter Fluke / 289C SHES500602 2020/06/12 to 2021/06/11 2021/06/06 to 2022/06/05 -- Matlab function SGS / RMS+POWER DIE.001461-1 2019/02/15 to -- -- Matlab function SGS / VoltageChangeMeasures DIE 001461-2 2019/02/15 to -- -- Matlab function SGS / Sequences DIE 001461-3 2019/03/07 to -- -- Matlab function SGS / Static+MobileWindow DIE 001461-4 2019/06/10 to -- -- Matlab function SGS / Parameter DIE 001461-5 2019/02/14 to -- -- Matlab function SGS / Rise&SettlingTime DIE 001461-6 2019/05/09 to --

Note:

1. All measurement equipment was used inside their corresponding calibration period. Copy of all calibration certificates are available at the laboratory for reference.

2. Since those Matlab functions are mathematical functions there is no need to establish a final calibration date.Report N. 2221 / 0124 - 1

Attachment I Page 11 of 327 Rev. 0 FRT test in FGW-TG3+SP1: Grid Fault Tests Results

2.4 MEASUREMENT UNCERTAINTY AND DATA SAMPLING RATES

Associated uncertainties through measurements showed in this this report are the maximum allowable uncertainties.

Magnitude Uncertainty Voltage measurement ±1.5 % Current measurement ±2.0 % Frequency measurement ±0.2 % Time measurement ±0.2 % Power measurement ±2.5 % Phase Angle ±1º Temperature ±3 ºC Note1: Measurements uncertainties showed in this table are maxi mum allowable uncertainties. The measurement uncertainties associated with other parameters measured during the tests are in the laboratory at disposal of the solicitant.

Power measurement ±2.5 % Phase Angle ±1º Temperature ±3 ºC Note1: Measurements uncertainties showed in this table are maxi mum allowable uncertainties. The measurement uncertainties associated with other parameters measured during the tests are in the laboratory at disposal of the solicitant. Note2: Where the standard requires lower uncertainties that those in th is table. Most restrictive uncertainty has been considered.

2.5 TEST SET UP

The test bench used includes:

Test bench Equipment Trademark / Model Serial number / ID Characteristics DC Source

ACTIONPOWER/

PVDS3-2.0K/2000C

DY18080090 DY18090103 2MW Per Unit DY18080093 DY18090102 AC Source

ACTIONPOWER/

PVDS3-2.0K/2000C PVAS3-331300/400C 1.3MVA Per Unit

Test bench requirements according to Annex D from the standard.Report N. 2221 / 0124 - 1 Attachment I Page 12 of 327 Rev. 0 FRT test in FGW-TG3+SP1: Grid Fault Tests Results

3 RESPONSE DURING GRID FAULTS

The aim of this test is to determinate whether the PGU is able to detect a voltage dip and to ride through this undamaged. This test has been done according to point 4.6 of the standard.

All the tests of this report have been performed with a deadband of Un ± 10 %Un. There is no command for negative sequence reactive current injection in any case.

The test has been carried out using a short circuit simulator which automatically adjusts the value of the series impedances and shot circuit impedances in order to obtain the type of fault configurated for each test.

At the electric scheme below, it can be seen the connection configuration for th is test, all the faults were simulated at the AC source.

series impedances and shot circuit impedances in order to obtain the type of fault configurated for each test.

At the electric scheme below, it can be seen the connection configuration for th is test, all the faults were simulated at the AC source.

In the page below it is provided a table with the test co nditions based on the table 4-688 and 4-69 of the FGW-TG3 standard.

The signals definitions for all the diagrams shown in the report are provided below.

  • R Voltage: Instantaneous phase-to-neutral voltages (phases 1-2). • S Voltage: Instantaneous phase-to-neutral voltages (phases 2-3). • T Voltage: Instantaneous phase-to-neutral voltages (phases 3-1). • R Current: Instantaneous phase current (phase 1). • S Current: Instantaneous phase current (phase 2). • T Current: Instantaneous phase current (phase 3). • RS RMS Voltage: RMS phase-to-phase voltage as moving averages over 20 ms (phases 1-2). • ST RMS Voltage: RMS phase-to-phase voltage as moving averages over 20 ms (phases 2-3). • TR RMS Voltage: RMS phase-to-phase voltage as moving averages over 20 ms (phases 3-1). • RS RMS Current: RMS phase current as moving averages over 20 ms (phase 1). • ST RMS Current: RMS phase current as moving averages over 20 ms (phase 2). • TR RMS Current: RMS phase current as moving averages over 20 ms (phase 3). • U+: Positive sequence voltage in per unit values. • IQ+: Positive sequence reactive current. • IP+: Positive sequence active current. • P+: Positive sequence active power as moving averages over 20 ms. • Q+: Positive sequence reactive power as moving averages over 20 ms. • U-: Negative sequence voltage in per unit values. • IQ-: Negative sequence reactive current. • IP-: Negative sequence active current.
  • P+: Positive sequence active power as moving averages over 20 ms. • Q+: Positive sequence reactive power as moving averages over 20 ms. • U-: Negative sequence voltage in per unit values. • IQ-: Negative sequence reactive current. • IP-: Negative sequence active current. • P-: Negative sequence active power as moving averages over

Estás viendo una vista previa

Lee el documento completo con Ariel

Este es un fragmento de uno de los más de 1.2 millones de documentos de la biblioteca de Ariel. Crea tu cuenta para leerlo completo, descargarlo y consultarlo con Ariel, que siempre te lleva a la fuente exacta: Ariel NO alucina.

Consultar sobre este documento ...