CNO - Sungrow Colombia Standard Declaration of Conformity LVRT HVRT CREG060 de 2024
CNO - Consejo Nacional de Operación
Descargar PDF
Disponible
Detalles
- Título
- CNO - Sungrow Colombia Standard Declaration of Conformity LVRT HVRT CREG060 de 2024
- Autor
- CNO - Consejo Nacional de Operación
- Categoría
- Infralegal
- Área del derecho
- Servicios Públicos
- Año
- 2024
Sungrow Power Supply Co., Ltd.
Add: No. 1699 Xiyou Rd., New & High Tech.
Industrial Development Zone, 230088, Hefei, China
Tel: +86 551 6532 7834
Email: info@sungrow.cn Website: www.sungrowpower.com 1 / 1
Conformity Declaration
Sungrow Power Supply Co. hereby declares compliance with the operating regulations to allow the connection and operation of solar photovoltaic plants in the SIN national interconnected system of Colombia. Specifically with the verification tests of the LVRT and HVRT performance curves required in CREG 060 of 2019 and CNO1223 agreement. Where it can be verified through the certifying agent performed by DEKRA and TÜVNord accredited under ISO/IEC 17065 for the certification of SG3125HV -30 inverters under IEC62910 and IEC61727 standards.
Verificación Apartado reporte No.6092407.51 Resultado Priorización de la inyección de corriente reactiva de forma que alcanza un 90% del delta de cambio esperado en menos de 50 ms, con una tolerancia del 20%, ante desviaciones de tensión que excedan los límites operativos de la tensión nominal en la planta de generación. Los 50 ms consideran el tiempo necesario para detectar la falla. 5.1, 5.2 Pasa Limitación del aporte de potencia reactiva adicional al 100% de la corriente nominal de cada generador. 5.1, 5.2 Pasa Sostenimiento del aporte de potencia reactiva adicional siempre que la tensión esté por fuera del rango normal de operación. 5.1, 5.2 Pasa Sostenimiento de la potencia reactiva durante 500 ms después de la tensión entre a la banda muerta de tensión manteniendo
siempre que la tensión esté por fuera del rango normal de operación. 5.1, 5.2 Pasa Sostenimiento de la potencia reactiva durante 500 ms después de la tensión entre a la banda muerta de tensión manteniendo un aporte adicional proporcional a la desviación de la tensión con respecto al valor de referencia (1p.u.). 5.1, 5.2 Pasa Si la ganancia k es configurable en cada inversor y en qué rango. Debe demostrarse que al menos es configurable entre 0 y 10. 5.1, 5.2. Test no muestra el rango de este valor. SG3125HV-30 configurable su factor k entre 0 y 10. Pasa El ajuste de la banda muerta. 5.1, 5.2 Pasa
Daniel Du Standard and Certification Engineer. January 1, 2023GNAS China National Accreditation Service for Conformity Assessment
PRODUCT CERTIFICATION BODY
ACCREDITATION CERTIFICATE
(Registration No. CNAS C183-P) TUV NORD (Hangzhou) Co., Ltd. Floor 5, No.50, Jiuhuan Road, Jiang Gan District, Hangzhou, P.R.China, 310019 to ISO/IEC 17065:2012 Conformity Assessment - Requirements for Bodies Certifying Products, Processes and Services (CNAS-CC02) for the competence to undertake the product certification service as described in the schedule attached to this certificate. The scope of accreditation is detailed ,n the attached schedule bearing the same registration number as above. The schedule forms an integral part of this certificate.
Date of lssue: 2020-11-10
Date of Expiry: 2025-11-23
Date of lnitial Accreditation: 2016-11-24 fi,.,. Signed on behalf of China National Accreditation Service for Conformity Assessment
integral part of this certificate.
Date of lssue: 2020-11-10
Date of Expiry: 2025-11-23
Date of lnitial Accreditation: 2016-11-24 fi,.,. Signed on behalf of China National Accreditation Service for Conformity Assessment / 1 China National Accreditatio n Service far Conformity Assessment (CNAS) is authorized by Certification and Accreditation Administration of the People's Republic of China (CNCA) to operate the national accreditation schemes far conformity assessment. CNAS is a signatory of the lnternational Accreditation Forum Multilateral Recognition Arrangement (IAF MLA) and the Asia Pacific Accreditation Cooperation Mutual Recognition Arrangement (APAC MRA).
The validity of the certificate can be checked on CNAS website at http://www.cnas.org.cn/english/findanaccreditedbody/index.shtml.File reference
PVP04005/20B-01
Certifica te of Conformity
Registered No.:
COCPVP04005/20B-01
Test report No.
TRPVP04005/20B/01
Date of issue 2020-04-17 On the basis of the tests undertaken, the samples of the below product(s) have been found to comply with the essential requirements of the referenced specifications at the time the tests were carried out:
Applicant: Manufacturer:
Product: Type designation:
Standard(s): Sungrow Power Supply Co., Ltd. No. 1699 Xiyou Road, New & High Technology Industrial Development Zone Hefei City, Anhui Province, 230088, P.R China Sungrow Power Supply Co., Ltd. No. 1699 Xiyou Road, New & High Technology Industrial Development Zone Hefei City, Anhui Province, 230088, P.R China Grid-connected PV inverter
SG3125HV-30
Test according to IEC 61727:2004 for PV lnverter. See test report for detailed information. This document is based on the evaluation of the samples of the above mentioned product(s). lt does
Grid-connected PV inverter
SG3125HV-30
Test according to IEC 61727:2004 for PV lnverter. See test report for detailed information. This document is based on the evaluation of the samples of the above mentioned product(s). lt does not imply an assessment of the mass-production of the product(s), and it does not permit the use of a TÜV NORD mark. The holder of this document may use it in connection with the related test report(s) Renewable Energy BOS-T-005 COC Page 1 of 1
TÜV NORD (HANGZHOU) CO., L TD.
Member of TÜV NORD Group
Tel: +86-571-85386989
Fax: +86-571-85386986
www.tuv-nord.com/cn P.R. China Version 1.1This is to attest that
DEKRA TESTING AND CERTIFICATION (SHANGHAI) LTD.
NO.250, JIANGCHANGSAN ROAD, JING’AN DISTRICT
SHANGHAI, 200436
PEOPLE’S REPUBLIC OF CHINA
Product Certification Agency PCA-141
has met the requirements of the applicable provisions of AC370, IAS Accreditation Criteria for Product Certification Agencies, has demonstrated compliance with ISO/IEC Standard 17065:2012, Conformity assessment - Requirements for bodies certifying products, process and services. This third-party product certification agency is accredited to provide the services specified in the scope of accreditation. Effective Date February 23, 2022
PresidentPCA-141 DEKRA Testing and Certification (Shanghai) Ltd.
Effective Date February 23, 2022 Page 2 of 5
IAS/PCA/100-1
DEKRA TESTING AND CERTIFICATION (SHANGHAI) LTD.
www.dekra.com.cn
Contact Name Wayne Wang Contact Phone +86-2160567603
Page 2 of 5
IAS/PCA/100-1
DEKRA TESTING AND CERTIFICATION (SHANGHAI) LTD.
www.dekra.com.cn
Contact Name Wayne Wang Contact Phone +86-2160567603 Accredited to ISO/IEC 17065:2012 Effective Date February 23, 2022
Product Category and Sub-Category Certification Scheme and Scheme Owner / Standard Low Voltage Electrical Equipment and Appliances DEKRA • Household and similar electrical appliances DEKRA Seal Scheme - Scheme Type 5 Certificate of Conformity (CoC) - Scheme Type 1a • Luminaires Certificate of Conformity (CoC) - Scheme Type 1a • Audio, video and similar electronic apparatus, information and communication technology equipment Certificate of Conformity (CoC) - Scheme Type 1a • Switches for appliances and automatic controls for electrical household appliances o Measuring relays and protection equipment Certificate of Conformity (CoC) - Scheme Type 1a Electrical Engineering DEKRA • Batteries o Primary batteries o Secondary cells and batteries containing alkaline or other non-acid electrolytes, Nickel systems o Secondary cells and batteries containing alkaline or other non-acid electrolytes, Lithium systems o Stationary electrical energy storage systems intended for connection to the low voltage grid o Stationary battery energy storage systems with lithium batteries Certificate of Conformity (CoC) - Scheme Type 1a • IT and Office Equipment Certificate of Conformity (CoC) - Scheme Type 1aPCA-141 DEKRA Testing and Certification (Shanghai) Ltd.
Effective Date February 23, 2022 Page 3 of 5
IAS/PCA/100-1
o Uninterruptible power systems (UPS) Electrical Engineering DEKRA • Electrical equipment for measurement, control, and laboratory use Certificate of Conformity (CoC) - Scheme Type 1a
Page 3 of 5
IAS/PCA/100-1
o Uninterruptible power systems (UPS) Electrical Engineering DEKRA • Electrical equipment for measurement, control, and laboratory use Certificate of Conformity (CoC) - Scheme Type 1a • Plug, socket outlets, cord extension set Certificate of Conformity (CoC) - Scheme Type 1a • Lamp control gear Certificate of Conformity (CoC) - Scheme Type 1a • Lamps Certificate of Conformity (CoC) - Scheme Type 1a • Transformers, reactors, power supply units and combinations Certificate of Conformity (CoC) - Scheme Type 1a • Installation Accessories and Connection Devices o Power electronic converter systems and equipment o Bi-directional grid-connected power converters Certificate of Conformity (CoC) - Scheme Type 1a • Low voltage, high power switching equipment o Low-voltage switchgear and control gear assemblies o PV Combiner Box Certificate of Conformity (CoC) - Scheme Type 1a • Cables and Cords o Cable management - Cable tray systems and cable ladder systems o Cable management systems – Cable ties for electrical installations o Cable cleats for electrical installations o Coaxial communication cables o Communication cable o Multicore and symmetrical pair/quad cables for digital communications o Optical fibre cables o Automotive cables Certificate of Conformity (CoC) - Scheme Type 1a • Installation Protective Equipment o Lightning protection system components (LPSC) o SPD multi-function(s) monitoring devices Certificate of Conformity (CoC) - Scheme Type 1aPCA-141 DEKRA Testing and Certification (Shanghai) Ltd.
Effective Date February 23, 2022 Page 4 of 5
IAS/PCA/100-1
Energy Efficiency DEKRA • Luminaires Certificate of Conformity (CoC) - Scheme Type 1a
Effective Date February 23, 2022 Page 4 of 5
IAS/PCA/100-1
Energy Efficiency DEKRA • Luminaires Certificate of Conformity (CoC) - Scheme Type 1a • Lamp control gear Certificate of Conformity (CoC) - Scheme Type 1a • Lamps Certificate of Conformity (CoC) - Scheme Type 1a • Household and similar electrical appliances Certificate of Conformity (CoC) - Scheme Type 1a • Photovoltaics o Power converters for use in photovoltaic power systems o PV inverter o Photovoltaic systems - Power conditioners o Grid connected photovoltaic inverters o Grid connected photovoltaic inverters or generator o Battery charge controllers for photovoltaic systems Certificate of Conformity (CoC) - Scheme Type 1a
Commission Regulation (EU) 2016/631 of 14 April 2016 establishing a network code on requirements for grid connection of generators. Rozporządzenie Komisji (UE) 2016/631 z dnia 14 kwietnia 2016 r. ustanawiające kodeks sieci dotyczący wymagań dotyczących przyłączenia wytwórców do sieci.
General Application Requirements resulting from the EU Commission Regulation 2016/631 of April 14, 2016 (PSE 2018-12-18) Wymogi Ogólnego Stosowania wynikające z rozporządzenia komisji UE 2016/631 z dnia 14 kwietnia 2016 r. ustanawiającego kodeks sieci dotyczący wymogów w zakresie przyłączenia jednostek wytwórczych do sieci - zatwierdzone Decyzją Prezesa Urzędu Regulacji Energetyki DRE.WOSE.7128.550.2.2018.ZJ z dnia 2 stycznia 2019 r.
Prezesa Urzędu Regulacji Energetyki DRE.WOSE.7128.550.2.2018.ZJ z dnia 2 stycznia 2019 r.
Conditions and procedures for the use of certificates in the process of connecting power generating modules to power grids. (PTPiREE 2021-04-28) Warunki i procedury wykorzystania certyfikatów w procesie przyłączenia modułów wytwarzania energii do sieci elektroenergetycznych Road Vehicle DEKRA
- Electrical Vehicles
o EV Charging System o EV On-Board Charger o Road Vehicles – Environment Condition o Electrically Propelled Road Vehicles —Electric Propulsion Components o EV charging coupler o Vehicle connectors o Vehicle high-voltage connectors Certificate of Conformity (CoC) - Scheme Type 1aPCA-141 DEKRA Testing and Certification (Shanghai) Ltd.
Effective Date February 23, 2022 Page 5 of 5
IAS/PCA/100-1
Miscellaneous DEKRA • Restriction of the use of certain Hazardous Substances in electrical and electronic equipment (RoHS) Certificate of Conformity (CoC) - Scheme Type 1a
Notes: The product certification used most closely resembles a product certification scheme type as described in ISO/IEC 17067 (2013), Conformity assessment — Fundamentals of product certification and guidelines for product certification schemes.
a. Type 1a: In this scheme, one or more samples of the product are subjected to the determination activities. A certificate of conformity or other statement of conformity (e.g. a letter) is issued for the product type, the characteristics of which are detailed in the certificate or a document referred to in the certificate. Subsequent production items are not covered by the certification body’s attestation of conformity. The samples are representative of subsequent production items which could be referred to by the manufacturer as being manufactured in accordance with the
Subsequent production items are not covered by the certification body’s attestation of conformity. The samples are representative of subsequent production items which could be referred to by the manufacturer as being manufactured in accordance with the certified type. The certification body may grant to the manufacturer the right to use the type certificate or other statement of conformity (e.g. letter) as a basis for the manufacturer to declare that subsequent production items conform to the specified requirements. b. Type 5: The surveillance part of this scheme allows for the choice between periodically taking samples of the product either from the point of production, or from the market, or from both, and subjecting them to determination activities to check that items produced subsequent to the initial attestation fulfill the specified requirements. The surveillance includes periodic assessment of the production process, or audit of the management system, or both. The extent to which the four surveillance activities are conducted may be varied for a gDEKRA Testing and Certification (Shanghai) Ltd.
Kreny Lin Certification Manager
© Integral publication of this attestation and adjoining reports is allowed Page 1 of 2
DEKRA Testing and Certification (Shanghai) Ltd. 3F #250 Jiangchangsan Road Shibei Hi-Tech Park, 200436 Jing'an District, Shanghai, China T +86 21 6056 7666 F +86 21 6056 7555 www.dekra-product-safety.com
ATTESTATION OF CONFORMITY
Issued to: Sungrow Power Supply Co., Ltd.
No.1699 Xiyou Rd., New & High Technology Industrial Development Zone, 230088, Hefei, P. R. China
For the product: Grid-connected PV inverter
Trade name:
Type/Model: SG3125HV-30, SG3125HV-31, SG3125HV-32
Ratings: See Annex
Manufactured by: Sungrow Power Supply Co., Ltd.
No.1699 Xiyou Rd., New & High Technology Industrial Development Zone, 230088, Hefei, P. R. China
Ratings: See Annex
Manufactured by: Sungrow Power Supply Co., Ltd.
No.1699 Xiyou Rd., New & High Technology Industrial Development Zone, 230088, Hefei, P. R. China
Requirements: IEC TS 62910:2020
This Attestation is granted on account of an examination by DEKRA, the results of which are laid down in a confidential file no. 6092407.51
The examination has been carried out on one single specimen or several specimens of the product, submitted by the manufacturer. The Attestation does not include an assessment of the manufacturer's production. Conformity of his production with the specimen tested by DEKRA is not the responsibility of DEKRA.
Arnhem, 23 December 2020 Number: 6092407.02AOCAnnex to 6092407.02AOC Page 2 of 2
Ratings of the test product: Operating temperature range: - 35° C to + 60° C Protective class: I Ingress protection rating: IP65 (Optional IP55) Power factor range (adjustable): 0.8 leading…0.8 lagging
SG3125HV-30: PV input: Max. 1500 Vdc, MPPT voltage range: 875-1300 Vdc, max current: 3997 A, Isc PV: 10000 A Output: 600V, 3~, 50/60 Hz, max 3308 A, rated 3125 kW, max 3437 kVA
SG3125HV-31: PV input: Max. 1500 Vdc, MPPT voltage range: 915-1300 Vdc, max current: 3997 A, Isc PV: 10000 A Output: 630V, 3~, 50/60 Hz, max 3308 A, rated 3125 kW, max 3610 kVA
SG3125HV-32:
Output: 630V, 3~, 50/60 Hz, max 3308 A, rated 3125 kW, max 3610 kVA
SG3125HV-32: PV input: Max. 1500 Vdc, MPPT voltage range: 960-1300 Vdc, max current: 3997 A, Isc PV: 10000 A Output: 660V, 3~, 50/60 Hz, max 3308 A, rated 3125 kW, max 3781 kVATRF No. IEC TS 62910_V1.0
Page 1 of 81
Test Report issued under the responsibility of:
TEST REPORT
IEC TS 62910
Utility-interconnected photovoltaic inverters - Test procedure for low voltage ride-through measurements Report Report Number. ................................ : 6092407.51 Date of issue .................................... : 2020-12-23 Total number of pages ...................... 81
Testing Laboratory ......................... : DEKRA Testing and Certification (Suzhou) Co., Ltd. Address ............................................ : No.99, Hongye Road, Suzhou Industrial Park, Suzhou, Jiangsu, P.R. China Applicant’s name ............................ : Sungrow Power Supply Co., Ltd. Address ............................................ : No.1699 Xiyou Rd., New & High Technology Industrial Development Zone, 230088, Hefei, P. R. China Test specification: Standard ........................................... : IEC TS 62910:2020 Test procedure ................................. : Type test Non-standard test method ................ : N/A Test Report Form No. ..................... : IEC TS 62910_V2.0 Test Report Form(s) Originator ........ : DEKRA Testing and Certification (Suzhou) Co., Ltd. Master TRF ...................................... : Dated 2020-08 Test item description ..................... : Grid-connected PV inverter Trade Mark ....................................... :
Manufacturer .................................... : Sungrow Power Supply Co., Ltd.
Master TRF ...................................... : Dated 2020-08 Test item description ..................... : Grid-connected PV inverter Trade Mark ....................................... :
Manufacturer .................................... : Sungrow Power Supply Co., Ltd. No.1699 Xiyou Rd., New & High Technology Industrial Development Zone, 230088, Hefei, P. R. China Model/Type reference ...................... : SG3125HV-30, SG3125HV-31, SG3125HV-32Page 2 of 81 Report No.: 6092407.51
TRF No. IEC TS 62910_V2.0
Ratings.............................................. : Operating temperature range: - 35°C to + 60°C Protective class: I Ingress protection rating: IP65 (Optional IP55) Power factor range (adjustable): 0.8 leading…0.8 lagging
SG3125HV-30: PV input: Max. 1500 Vdc, MPPT voltage range: 875-1300 Vdc, max current: 3997 A, Isc PV: 10000 A Output: 600V, 3~, 50/60 Hz, max 3308 A, rated 3125 kW, max 3437 kVA
SG3125HV-31: PV input: Max. 1500 Vdc, MPPT voltage range: 915-1300 Vdc, max current: 3997 A, Isc PV: 10000 A Output: 630V, 3~, 50/60 Hz, max 3308 A, rated 3125 kW, max 3610 kVA
SG3125HV-32: PV input: Max. 1500 Vdc, MPPT voltage range: 960-1300 Vdc, max current: 3997 A, Isc PV: 10000 A Output: 660V, 3~, 50/60 Hz, max 3308 A, rated 3125 kW, max 3781 kVAPage 3 of 81 Report No.: 6092407.51
max current: 3997 A, Isc PV: 10000 A Output: 660V, 3~, 50/60 Hz, max 3308 A, rated 3125 kW, max 3781 kVAPage 3 of 81 Report No.: 6092407.51
TRF No. IEC TS 62910_V2.0
Responsible Testing Laboratory (as applicable), testing procedure and testing location(s):
Testing Laboratory: DEKRA Testing and Certification (Suzhou) Co., Ltd.
Testing location/ address ................................ : No.99, Hongye Road, Suzhou Industrial Park, Suzhou, Jiangsu, P.R. China Associated Testing Laboratory: Shanghai Testing & Ispection Institute for Electrical Equipment Co.,Ltd Testing location/ address ................................ : No.505, Wuning Road, Putuo District,Shanghai, China Tested by (name, function, signature) ............ : Albert Liang
Approved by (name, function, signature) ....... : Jason Guo
Testing procedure: CTF Stage 1: Testing location/ address ................................ :
Tested by (name, function, signature) ............ : Approved by (name, function, signature) ....... :
Testing procedure: CTF Stage 2: Testing location/ address ................................ :
Tested by (name + signature) ........................ : Witnessed by (name, function, signature) ...... : Approved by (name, function, signature) ....... :
Testing procedure: CTF Stage 3: Testing procedure: CTF Stage 4: Testing location/ address ................................ :
Tested by (name, function, signature) ............ : Witnessed by (name, function, signature) ...... : Approved by (name, function, signature) ....... : Supervised by (name, function, signature) ..... :Page 4 of 81 Report No.: 6092407.51
TRF No. IEC TS 62910_V2.0
Approved by (name, function, signature) ....... : Supervised by (name, function, signature) ..... :Page 4 of 81 Report No.: 6092407.51
TRF No. IEC TS 62910_V2.0
Rating label: Page 5 of 81 Report No.: 6092407.51
TRF No. IEC TS 62910_V2.0
Warning Label: Page 6 of 81 Report No.: 6092407.51
TRF No. IEC TS 62910_V2.0
Test item particulars: Equipment mobility ........................................................ :
movable hand-held stationary fixed transportable for building-in Connection to the mains ............................................... : pluggable equipment direct plug-in permanent connection for building-in Enviromental category .................................................. : outdoor indoor indoor unconditional conditional Over voltage category Mains ........................................ : OVC I OVC II OVC III OVC IV Over voltage category PV ............................................. : OVC I OVC II OVC III OVC IV Mains supply tolerance (%) ........................................... : ±10% Tested for power systems ............................................. : TN IT testing, phase-phase voltage (V) .............................. : N/A Class of equipment ........................................................ : Class I Class II Class III Not classified Mass of equipment (kg) ................................................. : 3200 Pollution degree............................................................. : Outside PD3; Inside PD2 IP protection class ......................................................... : IP65 (Optional IP55) Possible test case verdicts: - test case does not apply to the test object ................. : N/A - test object does meet the requirement ....................... : P (Pass) - test object does not meet the requirement ................. : F (Fail) - this clause is information reference for installation .... : Info.
Testing: Date of receipt of test item ............................................ : 2020-10-25 (samples provided by applicant)
- test object does not meet the requirement ................. : F (Fail) - this clause is information reference for installation .... : Info.
Testing: Date of receipt of test item ............................................ : 2020-10-25 (samples provided by applicant) Date (s) of performance of tests ................................... : 2020-10-25 to 2020-11-30
General remarks: The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory. The measurement result is considered in conformance with the requirement if it is within the prescribed limit, It is not necessary to account the uncertainty associated with the measurement result. This report is only for reference and is not used for legal proof function in China market. The information provided by the customer in this report may affect the validity of the results, the test lab is not responsible for it. "(See Enclosure #)" refers to additional information appended to the report. "(see appended table)" refers to a table appended to the report.
Throughout this report a comma / point is used as the decimal separator.Page 7 of 81 Report No.: 6092407.51
TRF No. IEC TS 62910_V2.0
Name and address of factory (ies)
1. Sungrow Power Supply Co., Ltd.
No.1699 Xiyou Rd., New & High Technology Industrial Development Zone, Hefei 230088 P.R. China
2. Sungrow Power Supply Co., Ltd.
No. 608 Changning Avenue, New & High Technology Industrial Development Zone, Hefei 230088 P.R. China
3. Sungrow Developers (India) Private Limited No. 85, Kaniminike village, Kengeri hobli Bangalore South Taluk, 560074 Bangalore, IndiaPage 8 of 81 Report No.: 6092407.51
TRF No. IEC TS 62910_V2.0
General product information: Brief description:
560074 Bangalore, IndiaPage 8 of 81 Report No.: 6092407.51
TRF No. IEC TS 62910_V2.0
General product information: Brief description: The PCE under test (EUT) is Grid-Connected PV Inverter which utilizes the advanced power electronics
conversion components such as MosFET, IGBT, IPM to convert the variable DC power generated from the photovoltaic (PV) arrays to the stable utility AC power which can be fed into the commercial electrical grid. The PCE under test is three-phase Grid-Connected PV Inverter for solar power generation with the rated output power of 3125 kW. The external circuit breakers or fuses for PV array and Grid connection are required which the statements are provided in the installation manual.
Block Diagram:
The models SG3125HV-31, SG3125HV-30 are identical to SG3125HV-32 except for the model name and electrical ratings. Unless otherwise specified, all the tests were conducted on the basic model of SG3125HV-32 to represent the others.
The product was tested on: Firmware version:
DSP_SG3125HV-30_V1_A LCD_SG3125HV-30_V1_A Unless otherwise specified, all tests were conducted on basic model of SG3125HV-32 to represent the other models.Page 9 of 81 Report No.: 6092407.51
IEC TS 62910
Clause Requirement - Test Result - Remark Verdict
TRF No. IEC TS 62910_V2.0 4 Test circuit and equipment P 4.1 General P The circuits and equipment described in this clause are developed to allow tests that simulate the full range of anticipated grid faults, including: P • Single phase to ground fault (any phase) P • Two phase isolated fault, between any two phases P • Two phase grounded fault, involving any two phases P • Three phase short-circuit fault. P
anticipated grid faults, including: P • Single phase to ground fault (any phase) P • Two phase isolated fault, between any two phases P • Two phase grounded fault, involving any two phases P • Three phase short-circuit fault. P A full discussion of these faults and the resulting impact on voltage magnitude and phase angles is included in Annex A. P The short circuit emulator and grid simulator described in 4.3.3 and 4.3.4 are informative examples and are not intended to restrict design flexibility. Other designs may be used to achieve equivalent test functionality. The grid simulator used to achieve test of 4.3.4. P 4.2 Test circuit P The LVRT test circuit includes a DC source, the EUT, a grid fault simulator and the grid. A PV simulator (or PV array) provides input energy for the EUT. The output of the EUT is connected to the grid via a grid fault simulator, as shown in Figure 1.
PV array simulator and the grid simulator used in the LVRT test circuit. P 4.3 Test equipment P 4.3.1 Measuring instruments P Waveforms shall be measured by a device with memory function, for example, a storage or digital oscilloscope, or a high speed data acquisition device. Accuracy of the oscilloscope or data acquisition system should be at least 0.2% of full scale. The analogue to A/D of the measurement device shall have at least 12 bit resolution (in order to maintain the required measurement accuracy). PPage 10 of 81 Report No.: 6092407.51
IEC TS 62910
Clause Requirement - Test Result - Remark Verdict
TRF No. IEC TS 62910_V2.0
Voltage transducers (or voltage transformers) and current transducers (or current transformers) are the required sensors for measurement. The accuracy of the transducers
Clause Requirement - Test Result - Remark Verdict
TRF No. IEC TS 62910_V2.0
Voltage transducers (or voltage transformers) and current transducers (or current transformers) are the required sensors for measurement. The accuracy of the transducers should be 0.5 % of full scale or better. It is necessary to select the transducer measuring range depending on the normal value of the signal to be measured. The selected measuring range shall not exceed 150 % of the normal value of the measured signal. The transducer accuracy requirements are shown in Table 1
P 4.3.2 DC source P A PV array, PV array simulator or controlled DC source with PV characteristics may be used as the DC power source to supply input energy for the LVRT test. As the EUT input source, the DC power source shall be capable of supplying the EUT maximum input power and other power levels during the test, at minimum and maximum input operating voltages of the EUT. PV array simulator used as the DC power source to supply input energy. P The PV simulator should emulate the current/voltage characteristic of the PV module or PV array for which the EUT is designed. The response time of a PV simulator should not be longer than the MPP tracking response time of EUT. P For a EUT under test without galvanic isolation between the DC side and AC side, the output of the PV simulator shall not be earthed. P The equivalent capacitance between the output of the PV simulator and earth should be as low as possible in order to minimize the impact on the EUT. P A PV array used as the EUT input source shall be capable of matching the EUT input power levels specified by the test conditions. It is necessary to select a period of time in which the solar irradiance is stable and does not vary by more than 5 % during the test. P
P A PV array used as the EUT input source shall be capable of matching the EUT input power levels
Estás viendo una vista previa